Fire Door Inspection Checklist
Interactive fire door inspection checklist based on GOV.UK fire door guidance. Check door leaf, frame, seals, closer, gaps, and signage.
Door Leaf
Door leaf condition
No holes, cracks, broken panels, or delamination. Surface intact.
Fire rating label or plug visible
Certification label, colour-coded plug, or other evidence of fire rating (FD30 / FD60).
Glazing (if present) is fire-rated
Any glazed panels are fire-rated glass with intumescent seals. No cracks.
Frame
Frame in good condition
No damage, warping, or separation from wall. Fixings secure.
Intumescent strips present and intact
Strips fitted to door edge or frame rebate. Not painted over or damaged. If they were never fitted, the fire risk assessment decides whether that is acceptable (GOV.UK fire door guidance).
Cold smoke seals present and intact
Smoke seals (brush or blade type), where fitted, are not compressed or damaged. Some doors are rated without them; check the door’s rating.
Self-Closing Device
Self-closing device fitted
Overhead closer, concealed closer, or other approved device present. Not normally needed on cupboard or service-duct doors kept locked shut, or on doors within a flat or dwelling (Approved Document B, para C5). Entrance doors to flats and bedsit rooms always need one (LACORS para 21.5).
Door closes fully into frame from any angle
Test from fully open, 45°, and near-closed. Door must latch without manual assistance.
Door not held open (unless hold-open device)
No wedges, hooks, or improvised hold-open devices. Magnetic hold-open devices linked to fire alarm are acceptable.
Gaps and Clearance
Gaps at top and sides ≤ 4mm
No more than 4mm between door edge and frame on the hinge side, lock side and top: the industry standard cited in GOV.UK’s fire door guidance.
Gap at bottom as small as practicable
GOV.UK’s fire door guidance says the bottom gap should be as small as practicable while the door does not snag on the floor. Check the exact limit in the door’s certification.
Hardware
Hinges in good condition
All hinges secure, with no loose or missing screws. Check the number and type of hinges against the door’s certification.
Latch engages correctly
Latch holds door in closed position. Lock mechanism operates smoothly.
Signage
"Fire door keep shut" sign displayed (where needed)
Fire doors kept closed when not in use are normally marked on both sides. Approved Document B exempts doors to and within flats and dwellings, bedroom doors in hotels, hostels and similar, and lift doors. LACORS says room-door signs are usually unnecessary in a normal-risk shared house. Sign visible and legible.
"Fire door keep locked shut" (if applicable)
For fire doors kept locked when not in use, such as cupboards, stores and service risers. Cupboard and duct doors are marked on the outside.
Summary
Based on GOV.UK fire door guidance (Fire Safety (England) Regulations 2022), Approved Document B (Appendix C) and LACORS housing guidance. It does not reproduce BS 8214, which is not freely available, so check each door against its own certification. This checklist does not replace a full fire risk assessment.